Hostname: page-component-77c89778f8-m8s7h Total loading time: 0 Render date: 2024-07-19T17:28:24.406Z Has data issue: false hasContentIssue false

Partial discharge localization in power transformers based on the sequential quadratic programming-genetic algorithm adopting acoustic emission techniques

Published online by Cambridge University Press:  10 October 2014

Hua-Long Liu*
Affiliation:
School of Electrical Engineering, Wuhan University, Wuhan 430072, P.R. China
Hua-Dong Liu
Affiliation:
Institute of Network Technology, Beijing University of Posts and Telecommunications, Beijing 100876, P.R. China
Get access

Abstract

Partial discharge (PD) in power transformers is one of the prime reasons resulting in insulation degradation and power faults. Hence, it is of great importance to study the techniques of the detection and localization of PD in theory and practice. The detection and localization of PD employing acoustic emission (AE) techniques, as a kind of non-destructive testing, plus due to the advantages of powerful capability of locating and high precision, have been paid more and more attention. The localization algorithm is the key factor to decide the localization accuracy in AE localization of PD. Many kinds of localization algorithms exist for the PD source localization adopting AE techniques including intelligent and non-intelligent algorithms. However, the existed algorithms possess some defects such as the premature convergence phenomenon, poor local optimization ability and unsuitability for the field applications. To overcome the poor local optimization ability and easily caused premature convergence phenomenon of the fundamental genetic algorithm (GA), a new kind of improved GA is proposed, namely the sequence quadratic programming-genetic algorithm (SQP-GA). For the hybrid optimization algorithm, SQP-GA, the sequence quadratic programming (SQP) algorithm which is used as a basic operator is integrated into the fundamental GA, so the local searching ability of the fundamental GA is improved effectively and the premature convergence phenomenon is overcome. Experimental results of the numerical simulations of benchmark functions show that the hybrid optimization algorithm, SQP-GA, is better than the fundamental GA in the convergence speed and optimization precision, and the proposed algorithm in this paper has outstanding optimization effect. At the same time, the presented SQP-GA in the paper is applied to solve the ultrasonic localization problem of PD in transformers, then the ultrasonic localization method of PD in transformers based on the SQP-GA is proposed. And localization results based on the SQP-GA are compared with some algorithms such as the GA, some other intelligent and non-intelligent algorithms. The results of calculating examples both stimulated and spot experiments demonstrate that the localization method based on the SQP-GA can effectively prevent the results from getting trapped into the local optimum values, and the localization method is of great feasibility and very suitable for the field applications, and the precision of localization is enhanced, and the effectiveness of localization is ideal and satisfactory.

Type
Research Article
Copyright
© EDP Sciences, 2014

Access options

Get access to the full version of this content by using one of the access options below. (Log in options will check for institutional or personal access. Content may require purchase if you do not have access.)

References

Azevedo, C.H.B., Marques, A.P., Ribeiro, C.J., Methodology for the detection of partial discharges in power transformers using the acoustic method, in IEEE EUROCON 2009 (St.-Petersburg, Russia, 2009), pp. 618621CrossRefGoogle Scholar
Cintra Veloso, G.F. et al., Localization of partial discharges in transformers by the analysis of the acoustic emission, in IEEE ISIE 2006 (Montreal, Quebec, Canada, 2006), pp. 537541Google Scholar
Du, B.X. et al., PD localization based on fuzzy theory using AE detection techniques, in IEEE 2005 Annual Report Conference on Electrical Insulation and Dielectric Phenomena (Nashville, TN, USA, 2005), pp. 449452Google Scholar
Ashraf, S.A. et al., Modeling of acoustic signals from partial discharge activity, in IEEE GCC Conference 2006 (Manama, Bahrain, 2006), pp. 15Google Scholar
Liu, H.L., Journal of Chongqing University of Technology (Natural Science) 28, 71 (2014) [in Chinese]
Lundgaard, L.E., IEEE Elec. Insul. Mag. 8, 34 (1992)CrossRef
Liu, H.L., Journal of Chongqing University of Technology (Natural Science) 28, 109 (2014) [in Chinese]
Ma, L., Tao, P., Wireless Communication Technology 2013, 41 (2013) [in Chinese]
Yang, Y., Wang, B., Modern Electronics Technique 2007, 100 (2007) [in Chinese]
Kuo, Ch., Expert Syst. Appl. 36, 10304 (2009)CrossRef
Boczar, T. et al., IEEE Trans. Dielectr. Electr. Insul. 16, 214 (2009)CrossRef
Tang, L. et al., IEEE Trans. Dielectr. Electr. Insul. 15, 492 (2008)
Markalous, S.M., Tenbohlen, S., Feser, K., New robust non-iterative algorithms for acoustic PD-localization in oil/paper-insulated transformers, in 14th International Symposium on High Voltage Engineering 2005 (Beijing, China, 2005). Paper no. G-040Google Scholar
Kundu, P., Kishore, N.K., Sinha, A.K., Appl. Acoust. 70, 1378 (2009)CrossRef
Lu, Y., Tan, X., Hu, X., IEE Proc.-Sci. Meas. Technol. 147, 81 (2000)CrossRef
Hrstka, O., Kučerová, A., Adv. Eng. Softw. 35, 237 (2004)CrossRef
Goldberg, D.E., Genetic Algorithms in Search, Optimization and Machine Learning (Addison-Wesley Publishing Company, Massachusetts, USA, 1989)Google Scholar
Markalous, S.M., Tenbohlen, S., Feser, K., IEEE Trans. Dielectr. Electr. Insul. 15, 1576 (2008)CrossRef
Wu, Z., Master’s degree thesis, Huazhong University of Science and Technology, Wuhan, P.R. China, 2007
Dong, Z., Master’s degree thesis, Huazhong University of Science and Technology, Wuhan, P.R. China, 2011