Bacteriological evaluation of a mobile laminar cross-flow unit for surgery, under laboratory circumstances

Published online by Cambridge University Press:  15 May 2009

D. van der Waaij
Affiliation:
Radiobiological Institute TNO, Rijswijk, The Netherlands
N. Wiegersma
Affiliation:
Radiobiological Institute TNO, Rijswijk, The Netherlands
J. Dankert
Affiliation:
Department for Medical Microbiology, University Hospital, Groningen, The Netherlands
Rights & Permissions [Opens in a new window]

Summary

Core share and HTML view are not available for this content. However, as you have access to this content, a full PDF is available via the ‘Save PDF’ action button.

A mobile laminar cross-flow unit for surgery has been evaluated by the use of an experimental bacterial aerosol of Escherichia coli in different concentrations, generated at several different sites. A separate ventilation system, mounted underneath the table, produced an almost downward directed curtain of sterile air along both sides of the table. When the velocity of the air stream, discharged by the cross-flow unit, was adjusted at 0·50 m./sec. at 2 m. from the filter face (at the head end of the operation table), the surface of the table could be maintained free of bacterial settling, even after aerosolization of heavily concentrated suspensions of 108 bacteria/ml. at different sites outside the enclosure and underneath the table as well.

Type
Research Article
Copyright
Copyright © Cambridge University Press 1976

References

REFERENCES

Bernard, H. R., Speers, R., O'Grady, F. & Shooter, R. A. (1965). Reduction of dissemination of skin bacteria by modification of the operating-room clothing and by ultraviolet irradiation. Lancet ii, 458.Google Scholar
Foord, N. & Lidwell, O. M. (1972). The control by ventilation of airborne bacterial transfer between hospital patients, and its assessment by means of a particle tracer, I. Journal of Hygiene 58, 279.CrossRefGoogle Scholar
Hambraeus, A. (1973). Transfer of Staphylococcus aureus via nurses' uniforms. Journal of Hygiene 71, 799.Google Scholar
Lewis, H. E., Foster, A. R., Mullian, B. J., Cox, R. N. & Clark, R. P. (1969). Aerodynamics of the human microenvironment. Lancet ii, 1273.CrossRefGoogle Scholar
Lidwell, O. M. (1960). The evaluation of ventilation. Journal of Hygiene 58, 297.CrossRefGoogle ScholarPubMed
May, K. R. & Pomeroy, N. P. (1973). Bacterial dispersion from the body surface. In Airborne Transmission and Airborne Infection (ed. Hers, J. F. Ph. and Winkler, K. C.), p. 426. Utrecht: Oosthoek Publishing Co.Google Scholar
Van der Waaij, D., Heidt, P. J. & Hendriks, W. D. H. (1974). Bacteriological evaluation of a laminar cross-flow tunnel for surgery under operational conditions. Journal of Hygiene 72, 145.CrossRefGoogle ScholarPubMed
Van der Waaij, D., Vossen, J. M. & KorthalsAltes, C. Altes, C. (1973). Patient isolators designed in the Netherlands. In Germfree Research (ed. Heneghan, B.), p. 31. Academic Press.Google Scholar
Van der Waaij, D. & Van der Wal, J. F. (1973). Laminar air flow ventilation: cross-flow or down-flow? In Airborne Transmission and Airborne Infection (ed. Hers, J. F. Ph. and Winkler, K. C.), p. 584. Utrecht: Oosthoek Publishing Co.Google Scholar
Whyte, W. (1968). Bacteriological aspects of air-conditioning plants. Journal of Hygiene 66, 567.Google ScholarPubMed