Thermal comfort in warm and humid atmospheres: Observations on groups and individuals in Singapore

Published online by Cambridge University Press:  15 May 2009

F. P. Ellis
Affiliation:
Director Medical Research Council's Royal Naval Tropical Research Unit, Singapore
Rights & Permissions [Opens in a new window]

Extract

Core share and HTML view are not available for this content. However, as you have access to this content, a full PDF is available via the ‘Save PDF’ action button.

The majority of sedentary lightly clad acclimatized European men and women in Singapore are reasonably comfortable in relation to their indoor thermal environment provided the effective temperature does not exceed 78° F. or fall below 73° F.

European women, who were, however, older as a group than the other subjects, preferred rather cooler conditions than European men or Asian men and women.

There were considerable variations between individuals in their comfort tolerance for various levels of warmth, but the average opinion of one individual was usually consistent provided sufficient votes were collected to provide an adequate sample at each level of warmth.

When the dry-bulb temperature was above 83° F., increasing the average air movement from a still to a more turbulent condition added to the comfort of the majority of European men and women. When the temperature was below 83° F. for men and 81° F. for women, moderately good air movement was rather less comfortable than slight air movement; whereas below 77° F. still air was more comfortable than slight or moderate air movement. Increasing the air movement within a compartment can thus be used for combating thermal discomfort only within a limited range of warmth, but within that range it is extremely useful.

Two groups of naval ratings who had been living in a warship in a tropical climate were reasonably comfortable at similar levels of warmth to the men in Singapore, but they were less tolerant of levels of warmth above the comfort zone.

Type
Research Article
Copyright
Copyright © Cambridge University Press 1953

References

American Society of Heating and Ventilating Engineers'report 1196 of Technical Advisory Committee on Sensations of Comfort (1942). Trans. Amer. Soc. Heat. Vent. Engrs., 48, 107.Google Scholar
American Society of Heating and Ventilating Engineers (1950). Heating, Ventilating and Air-Conditioning Guide.Google Scholar
Baetjer, A. M. (1924). Threshold air currents in ventilation. Amer. J. Hyg. 4, 650.Google Scholar
Bedford, T. (1936). The warmth factor in comfort at work. Med. Res. Coun. Industr. Hlth Res. Bd. Rep. no. 76.Google Scholar
Bedford, T. (1946). Environmental warmth and its measurement. Med. Res. Coun. War Memo. no. 17. H.M.S.O.Google Scholar
Bedford, T. (1948). Basic Principles of Ventilation and Heating. London: H. K. Lewis.Google Scholar
Bedford, T. (1952). Heat and work. Research, 5, 155.Google Scholar
Behnke, A. R., Pace, N. & Consolazio, W. V. (1945). Physiological observations made on men in a ship during a shakedown cruise in tropical waters. U.S. Naval Medical Research Institute Report. Research Project X-205. Report no. 3.Google Scholar
Drysdale, J. W. (1950). Commonwealth Experimental Building Station, Sydney. Duplicated Document 32.Google Scholar
Ellis, F. P. (1952). Thermal comfort in warm and humid atmospheres. Observations in a warship in the tropics. J. Hyg., Camb. 50, 3, 415.CrossRefGoogle Scholar
Grocott, J. F. L. (1948). Comfort cooling in the tropics. J. Instn Heat. Vent. Engrs, 16, 36.Google Scholar
Houghten, F. C., Giesecke, F. E., Tasker, C. & Gutberlet, C. (1937). Cooling requirements for summer comfort air-conditioning. Proc. Amer. Soc. Heat. Vent. Engrs, 1055, p. 145.Google Scholar
Houghten, F. C. & Yaglou, C. P. (1923). Determining lines of equal comfort. Trans. Amer. Soc. Heat. Vent. Engrs, 29, 163.Google Scholar
Houghten, F. C. & Yaglou, C. P. (1924). Cooling effect in human beings produced by various air velocities. Trans. Amer. Soc. Heat. Vent. Engrs, 30, 193.Google Scholar
Rao, M. N. (1952). Comfort range in tropical Calcutta; a preliminary experiment. Ind. J. med. Res. 40, 45.Google Scholar
Yaglou, C. P. & Messer, Anne (1941). The importance of clothing in air conditioning. J. Amer. med. Ass. 117, 1261.CrossRefGoogle Scholar
Yaglou, C. P. & Miller, W. E. (1925). Effective temperature with clothing. J. Amer. Soc. Heat. Vent. Engrs, 31, 89.Google Scholar