16 - Summary and Conclusions

Summary

This work focuses attention on (i) incorporation of higher order harmonics in the analysis of relay tuning of controllers for a single loop controller, cascade control systems, single loop saturation relay test, single loop unstable FOPTD system and single loop stable SOPTD system; (ii) providing a simple method of designing P/PI controllers for cascade control schemes; (iii) estimation of model parameters of unstable FOPTD, stable SOPTD and unstable SOPTDZ systems using a single relay feedback test and (iv) application to multivariable systems.

Improved Autotune Identification Method

A method is suggested to formulate an additional equation so that the process gain can also be estimated using the conventional relay autotune method. This method avoids getting a negative time constant of an FOPTD model. For systems showing higher order harmonics in the response, a modification of the calculation for the model parameters of FOPTD model using the conventional relay feedback method is also proposed. This method does not assume the complete filtering of higher order harmonics. The method of calculation is also simple. The present method gives an improved value for the controller ultimate gain. The method gives a more accurate result [on ku and on the identified FOPTD model parameters] than that proposed by Luyben (1987) and Li et al. (1991). Simulation results show that the present method gives improved open loop as well as closed loop performances.

The proposed modification in the asymmetrical relay test gives improved values of the parameters of the FOPTD model.

Related content

Powered by UNSILO