Hostname: page-component-7bb8b95d7b-l4ctd Total loading time: 0 Render date: 2024-09-27T05:16:22.991Z Has data issue: false hasContentIssue false

A bronchoscopy-associated pseudo-outbreak of Mycobacterium chelonae and Mycobacterium mucogenicum associated with contaminated ice machine water and ice

Published online by Cambridge University Press:  05 June 2023

Drew W. Engers
Affiliation:
Section of Infectious Diseases, Department of Medicine, Trinity Health Ann Arbor, Ann Arbor, Michigan
Rajeev Swarup
Affiliation:
Section of Pulmonary, Department of Medicine, Trinity Health Ann Arbor, Ann Arbor, Michigan Veterans’ Affairs Hospital, Ann Arbor, Michigan
Cheryl Morrin
Affiliation:
Department of Infection Prevention and Control, Trinity Health Ann Arbor, Ann Arbor, Michigan
Mica Blauw
Affiliation:
Department of Infection Prevention and Control, Trinity Health Ann Arbor, Ann Arbor, Michigan Department of Infection Prevention and Control, Corewell Health. Grand Rapids, Michigan
Miles Selfridge
Affiliation:
Department of Engineering, Trinity Health Ann Arbor, Ann Arbor, Michigan
Pierre Gonyon
Affiliation:
Department of Engineering, Trinity Health Ann Arbor, Ann Arbor, Michigan
Janet E. Stout
Affiliation:
Special Pathogens Laboratory, Pittsburgh, Pennsylvania Department of Civil and Environmental Engineering, Swanson School of Engineering, University of Pittsburgh, Pittsburgh, Pennsylvania
Anurag N. Malani*
Affiliation:
Section of Infectious Diseases, Department of Medicine, Trinity Health Ann Arbor, Ann Arbor, Michigan Department of Infection Prevention and Control, Trinity Health Ann Arbor, Ann Arbor, Michigan
*
Corresponding author: Anurag N. Malani, Email: Anurag.Malani@trinity-health.org
Rights & Permissions [Opens in a new window]

Abstract

A pseudo-outbreak of bronchoscopy-associated Mycobacterium chelonae and M. mucogenicum was traced to contaminated ice machine water and ice. A nonsterile ice bath was used to cool uncapped, sterile, saline syringes used to slow procedural bleeding. Joining the growing evidence of bronchoscopy pseudo-outbreaks, our investigation describes several lessons for future prevention.

Type
Concise Communication
Copyright
© The Author(s), 2023. Published by Cambridge University Press on behalf of The Society for Healthcare Epidemiology of America

Bronchoscopy is a frequently utilized invasive procedure in the evaluation of pulmonary disease. Although efforts to mitigate infection risk with bronchoscopy are routinely employed, the ability to introduce exogenous microorganisms and possibly nosocomial infection has been well described. Prior reviews have characterized numerous bronchoscopy-related outbreaks and pseudo-outbreaks, highlighting issues such as inadequate disinfection practices and water contamination. Commonly identified organisms include Mycobacterium tuberculosis, nontuberculous mycobacteria (NTM), Pseudomonas aeruginosa, Serratia marcescens, and more recently, carbapenem-resistant Enterobacterales and other multidrug-resistant organisms. Reference Seoane-Vazquez, Rodriguez-Monguio, Visaria and Carlson1Reference Perkins, Reddy, Fagan, Arduino and Perz6 Of the aforementioned organisms, NTM presents unique challenges with its environmental presence in soil and water, including potable water in hospital settings. Reference Perkins, Reddy, Fagan, Arduino and Perz6Reference Kanamori, Weber and Rutala9

In this article, we review a pseudo-outbreak of NTM in a large teaching community hospital that was traced to a contaminated water source utilized during bronchoscopy procedures. In total, 15 patients who underwent bronchoscopy in September–October 2019 grew isolates of M. chelonae and M. mucogenicum. We describe the investigation of a pattern of unusual microbiology culture results, the molecular analysis confirming the link of NTM isolates from bronchial cultures to the contaminated ice machine, and implementation of processes to prevent further ice-machine–associated outbreaks and pseudo-outbreaks. Our investigation and response highlight opportunities to prevent similar bronchoscopy-related pseudo-outbreaks and outbreaks related to nonsterile water and ice.

Pseudo-outbreak investigation

The infection prevention (IP) team identified routine surveillance culture results from 4 separate bronchoscopy procedures around the same time with M. mucogenicum, an organism not previously reported at our institution from bronchoalveolar lavage (BAL) cultures. Given these atypical results, an investigation was triggered to identify whether this was an outbreak or pseudo-outbreak and to determine a potential source of the NTM.

Evaluation of culture methods by the microbiology laboratory revealed no evidence of contaminated cultures plates or other materials as a cause of the NTM. An inspection of the bronchoscopy suite was conducted by the IP and engineering teams with detailed review of the entire bronchoscopy process, facilities, equipment, storage, and staff responsibilities. Thorough examination of the postprocedural processing and high-level disinfection (HLD) was conductedn including precleaning steps, transportation and handling, manual cleaning of bronchoscopes and sinks, adenosine triphosphate testing before HLD, and HLD quality control measures and verification. Airflow in the processing areas was inspected. Maintenance schedules for bronchoscopes and automated endoscope reprocessing (AER) were assessed for adherence. Validation of staff training schedules for sterilization and disinfection, competency evaluations, and certificates showed no deficiencies.

Through this extensive review, an area of concern was the use of nonsterile ice machine water and ice to cool uncapped sterile water syringes in an ice water basin. The intended use of cooled sterile water syringes was to slow procedural bleeding if this occurred. Unfortunately, this process had the unintended consequences of not protecting the sterility of the prefilled syringes because they were ready for use without the cap and placed in the nonsterile ice bath. Notably, the ice-machine maintenance logs were up to date. Another potential source of the NTM was tap water, which was mixed with enzymatic solution during bronchoscope precleaning procedures. Cultures were subsequently collected from different water sources, including procedure room sinks, the ice machine water and ice, and water faucet fixtures, given concern for biofilms. These cultures were performed through Special Pathogens Laboratory (Pittsburgh, PA).

Initially, all bronchoscopies were halted for a couple days, and several steps were taken to prevent further cases. Sterilization of all 9 bronchoscopes was conducted by the central processing department rather than HLD in the endoscopy suite. Water restrictions were implemented; the use of nonsterile ice baths was discontinued; and point-of-use filters were placed on all procedure room faucets.

NTM case detection, molecular analysis, and whole-genome sequencing

Additional NTM cases were identified as the window of culture review expanded. During September–October 2019, 15 NTM isolates were identified from bronchoscopy cultures including 10 M. mucogenicum and 5 M. chelonae. All NTM were isolated from fungal BAL cultures. No BAL cultures of M. mucogenicum were identified prior to September 2019, and the most recent BAL culture prior to the outbreak window showing M. chelonae was processed in May 2019. Water testing results revealed M. mucogenicum from ice-machine ice (14 CFU/mL) and M. mucogenicum (>600 CFU/mL) and M. chelonae (>600 CFU/mL) from ice-machine water. With assistance from the Michigan Department of Health and Human Services (MDHHS), the Centers for Disease Control and Prevention (CDC) performed pulse-field gel electrophoresis (PFGE) and whole-genome sequencing (WGS) to evaluate similarities between the bronchial isolates and water and ice samples from the ice machine.

Two different types of NTM were connected to the ice-machine water source (Fig. 1). Overall, 9 bronchial cultures of M. mucogenicum had clonal relation to ice and water from the ice machine, and 3 bronchial isolates of M. chelonae were traced to water from the ice machine (Table 1). Another 3 isolates of M. mucogenicum or M. chelonae were not related to any of the other isolates according to PFGE. Of 11 isolates submitted for WGS, all 5 M. mucogenicum and 6 M. chelonae isolates appeared related to 2 distinct M. mucogenicum and M. chelonae clusters, respectively.

Fig. 1. Outbreak curve of Mycobacterium mucogenicum and Mycobacterium chelonae bronchosocpy cultures.

Table 1. Results of Pulsed-Field Gel Electrophoresis (PFGE) of 15 Nontuberculous (NTM) Isolates From Patients and an Ice Machine

Note. In total, 15 bronchial specimens had NTM, and 9 bronchial specimens with M. mucogenicum had the same genomic pattern as a cluster of M. mucogenicum isolated from ice in the ice machine (pattern 1, cluster A). Also, 3 bronchial specimens with M. chelonae had the same genomic pattern as M. chelonae identified from ice-machine water (pattern 2, cluster B). Furthermore, 3 bronchial specimens with NTM had unique patterns not isolated in any other specimen, either patient derived or from ice-machine testing.

Cultures from other potable water sources in the bronchoscopy procedure rooms yielded no growth of M. mucogenicum or M. chelonae. Unfortunately, specimens from the ice-machine water showing M. mucogenicum were not sent to the CDC and therefore were not included in the PFGE and WGS reports.

Patient impact and outcomes

Immediate and long-term plans were developed to address affected patients. Overall, there were 11 female and 4 male patients, aged 27–80 years, with wide ranging indications for bronchoscopy. Verbal disclosure to each patient was provided by a board-certified pulmonologist. The primary care physicians were also notified with written correspondence. A pulmonologist conducted medical chart reviews over the ensuing several months, with most patients having close pulmonary follow-up to assess their clinical status. At ∼1 year from the procedure, living patients received another follow-up pulmonologist telephone evaluation. No cases of true infection or clinical disease were encountered.

Discussion

Pseudo-outbreaks continue to occur in healthcare settings as previously demonstrated and described in this report. Frequently, these pseudo-outbreaks are bronchoscopy-associated and involve NTM. Reference Seoane-Vazquez, Rodriguez-Monguio, Visaria and Carlson1Reference Brown-Elliott and Philley10 Our experience highlights the importance of the IP team recognizing the anomaly of several BAL cultures showing similar NTM over a short period during routine surveillance. This cluster prompted a review of the entire bronchoscopy process, and an ice machine was found to be the water reservoir of M. chelonae and M. mucogenicum. Most healthcare-associated pseudo-outbreaks or infections of NTM are epidemiologically linked to a water source, including ice, ice water, tap water, distilled water, and water-based solutions. M. chelonae and M. mucogenicum, characterized as rapidly growing mycobacteria, are ubiquitous and are found both in the environment and in public and hospital water systems. Reference Brown-Elliott and Philley10

Corrective action included discontinuing any use of a nonsterile ice bath to cool sterile syringes. If medically necessary, cooled sterile saline syringes could be filled aseptically from a refrigerated sterile saline bottle or from a sealed bottle cooled by ice. In addition to the standard water filter (5 µm) for the water intake for the ice machine, a bacterial filter (0.20 µm) was also placed. To reduce the risk of further NTM pseudo-outbreaks and outbreaks, careful scheduled review and training of IP procedures and policies are essential in the bronchoscopy suite.

Acknowledgments

The authors thank Brenda Brennan MSPH, Noreen Mollon MS, and MDHHS for their assistance and coordination with the CDC for molecular typing and PFGE and WGS analyses. The authors thank Paige Gable MPH, Hollis Houston, Isaac Benowitz MD, Gillian McAllister, Alyssa Kent PhD, and Susannah McKay PhD, MPH and the CDC Clinical and Environmental Microbiology Branch and the CDC Genomics Sequencing Laboratory for performing the molecular typing and PFGE and WGS analyses.

Financial support

No financial support was provided relevant to this article.

Conflicts of interest

All authors report no conflicts of interest relevant to this article.

References

Seoane-Vazquez, E, Rodriguez-Monguio, R, Visaria, J, Carlson, A. Exogenous endoscopy-related infections, pseudoinfections, and toxic reactions: clinical and economic burden. Curr Med Res Opin 2006;22:20072021.CrossRefGoogle ScholarPubMed
Weber, DJ, Rutala, WA. Lessons learned from outbreaks and pseudo-outbreaks associated with bronchoscopy. Infect Control Hosp Epidemiol 2012;33:230234.CrossRefGoogle ScholarPubMed
Kovaleva, J, Peters, FT, van der Mei, HC, Degener, JE. Transmission of infection by flexible gastrointestinal endoscopy and bronchoscopy. Clin Microbiol Rev 2013;26:231254.CrossRefGoogle ScholarPubMed
Mehta, AC, Muscarella, LF. Bronchoscope-related “superbug” infections. Chest 2020;157:454469.CrossRefGoogle ScholarPubMed
Bringhurst, J, Weber, DJ, Miller, MB, et al. A bronchoscopy-associated pseudo-outbreak of Mycobacterium mucogenicum traced to use of contaminated ice used for bronchoalveolar lavage. Infect Control Hosp Epidemiol 2020;41:124126.CrossRefGoogle ScholarPubMed
Perkins, KM, Reddy, SC, Fagan, R, Arduino, MJ, Perz, JF. Investigation of healthcare infection risks from water-related organisms: summary of CDC consultations, 2014–2017. Infect Control Hosp Epidemiol 2019;40:621626.CrossRefGoogle ScholarPubMed
Phillips, MS, von Reyn, CF. Nosocomial infections due to nontuberculous mycobacteria. Clin Infect Dis 2001;33:13631374.CrossRefGoogle ScholarPubMed
Decker, BK, Palmore, TN. The role of water in healthcare-associated infections. Curr Opin Infect Dis 2013;26:345351.CrossRefGoogle ScholarPubMed
Kanamori, H, Weber, DJ, Rutala, WA. Healthcare outbreaks associated with a water reservoir and infection prevention strategies. Clin Infect Dis 2016;62:14231435.CrossRefGoogle ScholarPubMed
Brown-Elliott, BA, Philley, JV. Rapidly growing mycobacteria. Microbiol Spectr 2017;5(1). doi: 10.1128/microbiolspec.TNMI7-0027-2016.CrossRefGoogle ScholarPubMed
Figure 0

Fig. 1. Outbreak curve of Mycobacterium mucogenicum and Mycobacterium chelonae bronchosocpy cultures.

Figure 1

Table 1. Results of Pulsed-Field Gel Electrophoresis (PFGE) of 15 Nontuberculous (NTM) Isolates From Patients and an Ice Machine