Nosocomial Legionellosis Associated with Aspiration of Nasogastric Feedings Diluted in Tap Water

  • Richard A. Venezia (a1), Marjorie D. Agresta (a1), Eileen M. Hanley (a1), K. Urquhart (a2) and D. Schoonmaker (a3)...

Abstract

Problem:

Two cases of nosocomial legionellosis due to Legionella pneumophila serogroup 6 (Lp6) were identified in the intensive care unit. Both patients had a history of aspiration of nasogastric tube feedings, developed pulmonary infiltrates, had positive cultures for Lp6, had serological titer rises to Legionella, were treated, and recovered.

Method:

Isolates of Lp6 from the potable water system and patients were characterized by DNA restriction enzyme analyses using pulsed-field gel electrophoresis (PFGE).

Results:

Water samples grew >1O4 CFU/L of Lp6, and the same PFGE pattern was observed with the patient and water isolates. Potable water was used only for delivering medications and diluting feeding solutions given through the nasogastric tubes of the patients. Heat shock of the hot water system (140° to 160°F or 60° to 7O°C, 4 hours) was performed and the temperature was maintained between 131° to 140°F (55° to 60°C). Surveillance over 18 months revealed a reduction in Legionella to <102 CFU/L.

Conclusion:

We speculate that nosocomial Legionella pneumonia occurred due to aspiration of nasogastric tube solutions diluted with tap water. A nursing practice change to use only sterile water to dilute feedings and flush medications for nasogastric administration was instituted. The hot water temperature at the faucet was increased to ≥131°F (≥60°C) to control Legionella. No further nosocomial cases have occurred.

Copyright

Corresponding author

Department of Epidemiology, A-45, Albany Medical Center, Albany, NY 12208. 94-OA-02

References

Hide All
1.Vickers, RM, Yu, VL, Hanna, SS, et al. Determinants of Legionella pneumophilu contamination of water distribution systems: 15-hospital prospective study. Infect Control 1987;8:357363.
2.Alary, M, Joly, JR. Factors contributing to the contamination of hospital water distribution systems by Legionellae. J Infect Dis 1992;165:565569.
3.Bezanson, G, But-bridge, S, Haldane, D, et al. Diverse populations of Legionella pneumophilu present in the water of geographically clustered institutions served by the same water reservoir. J Clin Microbiol 1992;30:570576.
4.Blatt, SRParkinson, MD, Pace, E, et al. Nosocomial Legionnaires' disease: aspiration as a primary mode of disease acquisition. Am J Med 1993;95:1622.
5.States, JS, Conley, LF, Kuchta, JM, et al. Survival and multiplication of Legionella pneumophila in municipal drinking water systems. Appl Environ Microbiol 1987;53:979986.
6.Muraca, PW, Yu, VL, Goetz, A. Disinfection of water distribution systems for Legionella: a review of application procedures and methodologies. Infect Control Hosp Epidemiol 1990;11:7988.
7.Sanden, GN, Fields, BS, Barbaree, JM, et al. Viability of Legionella pneumophilu in chlorine-free water at elevated temperatures. Current Microbiol 1989;18:6165.
8.Hoge, CW, Breiman, RF, Advances in the epidemiology and control of Legionella infections. Epidemiologic Reviews 1991;13:329340.
9.Edelstein, PH. Legionnaires' disease. Clin Infect Dis 1993;16:741749.
10.Marrie, TJ, Haldane, D, Macdonald, S, et al. Control of nosocomial Legionnaires' disease by using sterile potable water for high risk patients. Epidemiol Infect 1991;107:591605.
11.Bopp, CA, Sumner, JW, Morris, GK, et al. Isolation of Legionella spp. from environmental water samples by low-pH treatment and use of selective medium. J Clin Microbiol 1981;13:714719.
12.Schoonmaker, D, Heimberger, T, Birkhead, G. Comparison of ribotyping and restriction enzyme analysis using pulsed-field gel electrophoresis for distinguishing Legionella pneumophilu isolates obtained during a nosocomial outbreak. J Clin Microbiol 1992;30:14911498.
13.Matulonis, U, Rosenfeld, CS, Shadduck, RK. Prevention of Legionella infections in a bone marrow transplant unit: multifaceted approach to decontamination of a water system. Infect Control Hospital Epidemiol 1993;14:571575.

Nosocomial Legionellosis Associated with Aspiration of Nasogastric Feedings Diluted in Tap Water

  • Richard A. Venezia (a1), Marjorie D. Agresta (a1), Eileen M. Hanley (a1), K. Urquhart (a2) and D. Schoonmaker (a3)...

Metrics

Altmetric attention score

Full text views

Total number of HTML views: 0
Total number of PDF views: 0 *
Loading metrics...

Abstract views

Total abstract views: 0 *
Loading metrics...

* Views captured on Cambridge Core between <date>. This data will be updated every 24 hours.

Usage data cannot currently be displayed