Airborne contamination in an operating suite: report of a five-year survey

  • Asakatsu Suzuki (a1), Yoshimichi Namba (a1), Masaji Matsuura (a2) and Akiko Horisawa (a1)

Summary

Airborne contamination in an operating suite was studied with a slit sampler, settle plates and a light-scattering particle counter. In conventional operating rooms there was a significant difference between the empty rooms and rooms in use; the mean total bacterial count by a slit sampler changed from 1·1 in empty to 42·5 c.f.u./m3 in use (39 times increase), the settle plates count changed from 1·5 to 17·4 c.f.u./m2/min (12 times increase), and the mean total particle count changed from 56·9 to 546·7/1 (10 times increase) respectively. The increase was caused mainly by persons present in the room.

Another difference was found between zones in the operating suite; the bacterial count in the clean area doubled in the semi-clean area and further doubled in the dirty area in slit sampler count as well as settle plates count, and particle count in the clean area increased by 14 times in the semi-clean and dirty areas. This difference resulted from the different quality of the ventilating system.

Air cleanliness of operating rooms in use by persons present in the room dropped to a level between the clean and the semi-clean area in spite of the high quality of the ventilating system.

Bacterial species identified were mostly coagulase negative staphylococci and micrococci.

Our study indicates that reduction of airborne contamination in an operating suite is accomplished by the combination of an efficient ventilating system and the restriction of the number of persons present in the room.

    • Send article to Kindle

      To send this article to your Kindle, first ensure no-reply@cambridge.org is added to your Approved Personal Document E-mail List under your Personal Document Settings on the Manage Your Content and Devices page of your Amazon account. Then enter the ‘name’ part of your Kindle email address below. Find out more about sending to your Kindle. Find out more about sending to your Kindle.

      Note you can select to send to either the @free.kindle.com or @kindle.com variations. ‘@free.kindle.com’ emails are free but can only be sent to your device when it is connected to wi-fi. ‘@kindle.com’ emails can be delivered even when you are not connected to wi-fi, but note that service fees apply.

      Find out more about the Kindle Personal Document Service.

      Airborne contamination in an operating suite: report of a five-year survey
      Available formats
      ×

      Send article to Dropbox

      To send this article to your Dropbox account, please select one or more formats and confirm that you agree to abide by our usage policies. If this is the first time you use this feature, you will be asked to authorise Cambridge Core to connect with your <service> account. Find out more about sending content to Dropbox.

      Airborne contamination in an operating suite: report of a five-year survey
      Available formats
      ×

      Send article to Google Drive

      To send this article to your Google Drive account, please select one or more formats and confirm that you agree to abide by our usage policies. If this is the first time you use this feature, you will be asked to authorise Cambridge Core to connect with your <service> account. Find out more about sending content to Google Drive.

      Airborne contamination in an operating suite: report of a five-year survey
      Available formats
      ×

Copyright

References

Hide All
Bengtsson, S., Hambraeus, A. & Laurell, G. (1979). Wound infection after surgery in a modern operating suite: clinical and epidemiological findings. Journal of Hygiene 83, 4157.
Charnley, J. (1972). Postoperative infection after total hip replacement with special reference to air contamination in the operating room. Clinical Orthopaedics and Related Research 87, 167187.
Fitzgerald, R. H. (1979). Microbiologic environment of the conventional operating room. Archives of Surgery 114, 772775.
Lidwell, O. M., Lowbury, E. J. L., Whyte, W., Blowers, R., Stanley, S. J. & Lowe, D. (1982). Effect of ultraclean air in operating rooms on deep sepsis in the joint after total hip or knee replacement: a randomised study. British Medical Journal 285, 1014.
Lidwell, 0. M., Lowbury, E. J. L., Whyte, W., Blowers, R., Stanley, S. J. & Lowe, D. (1983). Airborne contamination of wounds in joint replacement operations: the relationship to sepsis rates. Journal of Hospital Infection 4, 111131.
Noble, W. C., Lidwell, O. M. & Kingston, D. (1963). The size distribution of airborne particles carrying micro-organisms. Journal of Hygiene 61, 385391.
Whyte, W., Lidwell, O. M., Lowbury, E. J. L. & Blowers, R. (1983). Suggested standards for air in ultraclean operating rooms. Journal of Hospital Infection 4, 133139.

Airborne contamination in an operating suite: report of a five-year survey

  • Asakatsu Suzuki (a1), Yoshimichi Namba (a1), Masaji Matsuura (a2) and Akiko Horisawa (a1)

Metrics

Full text views

Total number of HTML views: 0
Total number of PDF views: 0 *
Loading metrics...

Abstract views

Total abstract views: 0 *
Loading metrics...

* Views captured on Cambridge Core between <date>. This data will be updated every 24 hours.

Usage data cannot currently be displayed